Equipment category
BESS
Battery energy storage at depot/site
Faults (10)
DEP-ISLANDSite stack (generic) · BESS solo+Island mode leaves EVSE dark
Island mode leaves EVSE dark — site generation/BESS island excludes EVSE bus or opens intertie. site-generic field note:…
BESS-UVFluence / BESS · BESSFree sampleBESS undervoltage at cabinet
Fluence BESS reports an undervoltage (UV) inhibit at the EVSE feed — either the PCS AC output or the shared DC bus — so dependent chargers brown out mid-session or latch Faulted while the BESS HMI independently alarms UV. It shows up most on hot afternoons when several dispensers ramp together and SOC is already drawn down from an overnight fleet pull, so the first minutes of triage are about proving whether the EVSE is really broken or the depot just asked for more than the BESS could deliver at that SOC.
BESS-OVFluence / BESS · BESS solo+BESS overvoltage trip
Fluence BESS overvoltage (OV) protection trips and opens the discharge/charge path feeding the EVSE bus, so dependent di…
BESS-INTFluence / BESS · BESS solo+BESS interlock open
A BESS interlock — door switch, E-stop, or maintenance key — is open and removing EVSE feed permission, so chargers appe…
BESS-THERMFluence / BESS · BESS solo+BESS thermal runaway alarm
The BESS reports a thermal runaway alarm or a critical thermal inhibit that locks out the EVSE feed and may trigger the …
BESS-COMFluence / BESS · BESS solo+BESS EMS comms loss
The BESS EMS loses communication with the PCS, site network, or historian, and depending on the failsafe configuration t…
BESS-SOCFluence / BESS · BESS solo+SOC floor blocks EVSE feed
The BESS SOC floor is blocking EVSE feed exactly as designed — the system will not discharge below its configured minimu…
BESS-PCSFluence / BESS · BESS solo+PCS fault blocks discharge to EVSE
A power conversion system (PCS) fault opens the contactors that connect the BESS to the EVSE bus, so chargers lose their…
BESS-FIREFluence / BESS · BESS solo+Fire panel inhibits charge
The fire alarm control panel (FACP) is holding an inhibit on the BESS/EVSE charge and discharge path, locking out charge…
BESS-BALFluence / BESS · BESS solo+Cell imbalance inhibits output
Cell or module imbalance within the BESS is limiting or fully blocking discharge output to the EVSE bus, so chargers eit…