The EVSE Directory · Field sheet · Cross-brand / Protocol · LOAD-02
LOAD-02Free sampleLMS heartbeat lost — failsafe curtail
Cross-brand / Protocol · Power cabinet / LMS
Safety
Coordinate with site power ops before overriding failsafe.
How it presents
Symptom
LMS heartbeat lost — failsafe curtail — chargers derate or go Unavailable when site LMS/PLC heartbeat drops, protecting the feeder. protocol field note: keep evidence scrubbed and prove the ranked cause before module RMA on LOAD-02.
Root causes (by observed frequency)
- #1 LMS PLC offline or network path to chargers down
Failsafe is working
- #2 Wrong LMS IP/VLAN after switch change
- #3 Heartbeat timeout set too tight for loaded network
- #4 Charger LMS client fault after FW update
Diagnostic procedure
1. Read LMS online status and allocated amps
Expected: Offline → failsafe amps
Tools: LMS
2. Ping/path-check LMS from charger VLAN
Expected: Reachable
Tools: IT
3. Verify charger LMS client config (IP, ID)
Expected: Matches commissioning
Tools: HMI
4. Restore PLC/network; watch amps recover
Expected: Budget returns
Tools: LMS
5. Only then chase single-stall EVSE faults
Tools: field
The fix
Failsafe curtail on lost LMS heartbeat is site controls — restore LMS before EVSE RMA.
- Treat pad-wide curtail as LMS/network until proven otherwise.
- Restore LMS PLC and VLAN path. Document readings and scrubbed photos for LOAD-02 before closing the ticket.
- Correct charger LMS client settings after switch/FW changes.
- Retune heartbeat timeouts with controls engineering if flapping.
- Validate allocated amps and a live session after restore.